| RTU Name |
This is the name used to identify this RTU. |
| Configuration |
Select the configuration that this RTU should
use. New configurations are added on the server. |
| Comms Protocol |
Specify the communications protocol required
to talk to the RTU. The following protocols are supported: Serial / TCP
/ Modem / Acquire. The selected protocol will determine the setup fields
displayed |
| IP Address (TCP Only) |
This is the IP address of the RTU. |
| TCP Port (TCP Only) |
This is the TCP port of the RTU. For Modbus
TCP this is normally 502. |
| Telephone No (Modem Only) |
This is the telephone number to dial to contact
the RTU. |
| Baud Rate (Serial / Modem) |
This is the baud rate of the serial port used to connect
to the RTU. |
| Data Bits (Serial / Modem) |
This is the number of data bits of the serial
port connection. It is normally set to 8. |
| Stop Bits (Serial / Modem) |
This is the number of stop bits of the serial
port connection. It is normally set to 1. |
| Parity (Serial / Modem) |
This is the parity setting of the serial port
connection. It is normally set to NONE. |
| Slave Address |
This is the Modbus slave address that the
RTU will respond on. It is normally set to 1. If you are using multi drop
RS422 then each RTU will have its own unique Modbus slave address. |
| RTU Timeout |
This is the length of time in seconds that
Profile will wait for a response from the RTU. To use the default settings
enter 0 in to this field. |
| RTU Connection Timeout |
This is the length of time in seconds that
Profile will wait for a connection to be made. To use the default settings
enter 0 into this field. |
| RTU Stream |
This bit will change on the final release. |
| Collect Alarms Every |
This popup menu allows you to override the
default rate that alarms are requested for the RTU. The default poll rate
is 2 seconds although this default poll rate can be modified in the Profile
preferences screen. |
| Collect Chart Data Every |
This popup menu allows you to override the
default rate that historical data is gathered for the chart etc. The default
poll rate is 1 minute although this default poll rate can be modified in
the Profile preferences screen. |